Transformer Turns Ratio and Full-Load Current Calculator
Find the turns ratio, the full-load current on the primary and secondary, and the fault current on the secondary of a transformer.
Engineering student calculators
Free textbook calculators with every step shown, so you can check your own working. Pick one, type in your numbers and see the formulas worked out. Or switch to Ask a question for an explained answer. No account needed.
Calculated from standard textbook formulas, with every step shown. The formulas are fixed, so the working does not need checking: what matters is the numbers you type in. Use these calculators only if you are competent to choose the inputs (loads, material strength, dimensions, supports) and check your units and assumptions. For learning and checking your own working: design and sign-off are for a qualified engineer. Drafting Central does not store the numbers you type.
How this calculator works
The voltage ratio of a transformer equals its turns ratio. The full-load current is the kVA divided by the voltage, and for a three-phase transformer also by root three.
The percentage impedance on the nameplate is the voltage drop across the transformer at full load. The fault current on the secondary is the full-load current divided by that percentage as a fraction.
Formulas used
- \dfrac{V_1}{V_2} = \dfrac{N_1}{N_2}
- I_{FL} = \dfrac{S}{\sqrt{3}\,V_L}
- I_{sc} = \dfrac{I_{FL}}{Z\%/100}
Worked example
With the default numbers in the calculator above:
- Turns ratio: 26.51 : 1
- Full-load current, primary: 52.49 A
- Full-load current, secondary: 1391.21 A
- Fault current on the secondary (supply taken as infinite): 27824.11 A
- Fault current on the primary: 1049.73 A
Change the numbers in the calculator to see the full working, every step, for your own case.
Common questions
Is this the real fault current?
It is the upper figure, assuming the supply behind the transformer is infinite. The real figure is a little lower and is lower still along a cable.
What is a typical percentage impedance?
Distribution transformers are commonly in the range 4 to 6 percent. Read the nameplate.
Related calculators
Further reading: Standard electrical engineering texts (transformers). Switchgear must be selected by a licensed person.
Need a calculator we do not have?
Embed this calculator on your own page
Copy this code into your page. The calculator runs inside the frame and links back to Drafting Central.
Need this drawn, designed or checked?
Drafting Central is a mechanical engineering and drafting business in Burleigh Waters on the Gold Coast. A calculator gives you the numbers; we can turn them into drawings and designs.
Need help with a real project?
Talk to Drafting Central →