Heat Pump and Chiller COP Calculator: Capacity and Running Cost against Outdoor Temperature

An estimate of how the COP and capacity of an air-source heat pump or chiller change with the outdoor temperature, and what it costs to run.

Calculated from standard textbook formulas, with every step shown. The formulas are fixed, so the working does not need checking: what matters is the numbers you type in. Use these calculators only if you are competent to choose the inputs (loads, material strength, dimensions, supports) and check your units and assumptions. For learning and checking your own working: design and sign-off are for a qualified engineer. Drafting Central does not store the numbers you type.

How this calculator works

A heat pump moves heat from a cold source to a warm destination, and the bigger the temperature difference it works across, the harder it works. The most efficient a machine can ever be between two temperatures is the Carnot COP. A real machine reaches a share of it, about 0.4 to 0.55 for a good air-source machine.

The calculator takes the outdoor air temperature and the delivery temperature, allows a temperature approach at each heat exchanger (the evaporator must be colder than the outdoor air and the condenser hotter than the delivery temperature), finds the Carnot COP between them, and multiplies by the share you enter.

The capacity of a heat pump also falls as the outdoor air gets colder, just when the building needs most heat. The calculator estimates this from the rated capacity at 7 degrees and a percentage change per degree, so you can see whether the machine covers the load on the coldest day and what it costs to run. These figures are estimates: the maker's data for the real machine always wins.

Formulas used

  • COP_{Carnot,heat} = \frac{T_c}{T_c - T_e}
  • COP_{Carnot,cool} = \frac{T_e}{T_c - T_e}
  • COP = \varepsilon_C\,COP_{Carnot}
  • P = Q_d / COP

Worked example

With the default numbers in the calculator above:

  1. Evaporating and condensing temperatures (with the approach): -6 and 48 °C
  2. Carnot COP between them: 5.947
  3. Estimated COP of the machine: 2.676
  4. Electrical power to meet the load: 7.473 kW
  5. Capacity at this outdoor temperature: 21.88 kW
  6. Running cost at this load: 17.94 $/day

Change the numbers in the calculator to see the full working, every step, for your own case.

Common questions

Why is a low delivery temperature better?

The temperature lift is smaller, so the COP is higher. A floor heating or fan coil system at 35 degrees gives a much better COP than radiators at 60 degrees.

What COP should I expect?

It depends on the machine and the temperatures. Use the maker's data at your outdoor and delivery temperatures; this tool shows the trend.

Does it include defrost?

No. Defrost cycles in cold, damp weather lower the real average COP and capacity.

Related calculators

Further reading: ASHRAE Handbook: HVAC Systems and Equipment; Cengel and Boles, Thermodynamics: An Engineering Approach; Moran and Shapiro, Fundamentals of Engineering Thermodynamics.

Need a calculator we do not have?

Tell us what you would like to calculate. We read every request and build the most asked-for ones.

We store your request (and your email if you give it) to decide what to build. We do not store the numbers you type into calculators.

Embed this calculator on your own page

Copy this code into your page. The calculator runs inside the frame and links back to Drafting Central.

Need this drawn, designed or checked?

Drafting Central is a mechanical engineering and drafting business in Burleigh Waters on the Gold Coast. A calculator gives you the numbers; we can turn them into drawings and designs.

Need help with a real project?

Talk to Drafting Central →

← All engineering calculators